621-2102R

In Stock


In Stock

115VAC Output- 8 point

8-Point, 115 Vac Self-Protected Discrete Output Module

621-2102R
Outputs8

Output On at zero crossing
Voltage Range90-140 Vac
Surge Current15 A, 2 cycle

(nonrepetitive)
Off-State

Leakage Current
<=5 mA (typical)
On-State

Voltage Drop
<=2 Vac at 2 A
Fusing3 A slo-blo
Operating Current

+5 Vdc
130 mA plus 24 mA

for each energized

output, 322 mA max
Addressing
Terminal Block

Required
621-9949

Operation:
The model 621-2102R compares the status of the output triac with the Control Processor Module (CPU) signal. When the two signals do not compare, the module indicates a malfunction.

Scroll to Top