621-6650R

Low Stock


Low Stock

Output Module 48VDC

Power Derating
Applications requiring voltages of more than 48VDC may require derating according to the ambient temperature
(60?C maximum) of the rack.

CAUTION
— Exceeding the recommended number of ON outputs may damage the module.
—Applications requiring voltages of more than 48VDC should not operate above 140?F (60?C), or damage may occur to components.


621-6650R
Outputs16
Points Per

module
16
Voltage Range38-66 Vdc
Maximum

Current Range
2A per circuit,

5A per group

of 4, 12A permodule
Surge Current8 A for 10ms
Field Power

Requirement
25 mA for each

energized output
Off-State

Leakage Current
<=5 mA (typical)
On-State

Voltage Drop
<=2 Vdc at 2 A

Scroll to Top